Transformer detection High voltage withstand test equipment Switch detection equipment electric energy measurement and testing equipment secondary circuit test equipment Lightning arrester/insulator testing equipment Ground/Insulation Resistance Test Equipment SF6Gas detection category Phase voltammeter Frequency conversion grounding grid grounding resistance tester Digital intelligent partial discharge tester Vacuum degree Micro water meter Insulating oil dielectric strength tester Insulating oil micro-water tester Wired vector Flatbed Vector Analyzer Taiqu District User Identifier Cable fault detector Generator rotor AC impedance tester Dielectric loss tester Nuclear phase analyzer Electric energy meter field calibrator Underground pipeline detector AJRZTransformer short circuit impedance tester Oil and water tester Transformer short circuit impedance tester DC resistance tester Generator AC impedance Battery testing equipment
AJ605 Transformer on-load switch tester
1、 Product Overview:
The transformer on load tap changer tester is a high-voltage testing equipment designed according to the power industry standards of the People's Republic of China, with general technical conditions DL/T846 and 8-2004. It can meet the requirements of the "Code for Handover and Preventive Testing of Power Equipment", such as checking the action sequence of on load tap changers and measuring switching time. It can achieve accurate measurement of parameters such as transition time, transition waveform, transition resistance, and three-phase synchronicity of on load tap changers, making it an ideal device for testing on load tap changers. (If the user is a load switch for capacity adjustment, please inform in advance)
2、 Main features:
①. Test the Y0 Y △ transformer, and display the resistance value directly without conversion;
②. Humanized data analysis can automatically identify faults in the middle of the waveform and mark them;
③. The waveform display automatically adjusts the amplitude of resistance and time based on the sampled data;
④. △ - type transformers can display three-phase synchronicity;
⑤. Can be tested with or without windings;
⑥. Four terminal wiring method, providing high-precision resistance measurement without the need for wire compensation;
⑦. Continuous testing can be conducted during the testing process to save time on transformer power outages;
⑧ The instrument can generate Word reports for easy data management and retrieval;
⑨. The instrument is controlled by a small computer, equipped with an 800 × 480 color LCD touch screen, high-speed printer, and supports external mouse for easy operation;
⑩. The instrument can automatically save 1000 sets of data internally, or it can be saved externally with a USB flash drive.
3、 Technical parameters:
①. Three phase constant current source charging, charging current: 3A/1A range; 0.6A/0.2A gear
②. Maximum voltage of port: 24V
③. Maximum range of transition resistance: 100 Ω
④. Transition resistance measurement range: 1A range: 0.4 Ω~20 Ω 0.2A range: 10 Ω~100 Ω
⑤. Duration of waveform recording: 300ms
⑥. Sampling rate: 30k
⑦. Time resolution: 0.1ms
⑧. Resistance resolution: 0.1 Ω
⑨. Accuracy: Transition resistance: ± 5% reading ± 0.1 Ω Transition time: ± 0.5% reading ± 0.2mS
⑩. Operating temperature: -10~40 ℃ Operating relative humidity:<85% RH Instrument weight: 15KG