Transformer detection High voltage withstand test equipment Switch detection equipment electric energy measurement and testing equipment secondary circuit test equipment Lightning arrester/insulator testing equipment Ground/Insulation Resistance Test Equipment SF6Gas detection category Phase voltammeter Frequency conversion grounding grid grounding resistance tester Digital intelligent partial discharge tester Vacuum degree Micro water meter Insulating oil dielectric strength tester Insulating oil micro-water tester Wired vector Flatbed Vector Analyzer Taiqu District User Identifier Cable fault detector Generator rotor AC impedance tester Dielectric loss tester Nuclear phase analyzer Electric energy meter field calibrator Underground pipeline detector AJRZTransformer short circuit impedance tester Oil and water tester Transformer short circuit impedance tester DC resistance tester Generator AC impedance Battery testing equipment
AJDBP Multi frequency induction withstand voltage experimental device
1、 Technical parameters
1. Capacity: 15kVA.
2. Input voltage: AC, three-phase, 300V ± 10%. (Note: Single phase 220V can also be connected).
3. Power frequency: 50Hz.
4. Output voltage: 0-380V (voltage can be increased after adding a step-up transformer, additional configuration).
5. Output frequency: 50Hz, 100Hz, 150Hz, 200Hz, 250Hz (optional), can also be set by oneself.
6. Waveform distortion rate:<3%.
2、 Device characteristics and working principle
The device adopts power electronics technology, and the internal core part uses a variable frequency regulator. Parameter presetting, protection settings, frequency selection, voltage regulation control, etc., all adopt digital control technology. Built in computer, 7-inch color LCD display, data storage can reach 200 sets.
Adopting a touch based operation method.
The test frequencies of 50Hz, 100Hz, 150Hz, 200Hz, and 250Hz can be preset (optional), and the voltage can be adjusted by touch (the step size can be adjusted in real time, selecting 1V, 2V, 5V), which can achieve multi frequency test voltage output of this device.
External LC filtering circuit ensures that the waveform distortion rate is within the specified range. External compensation inductance with tap to compensate for the capacitance current of the tested equipment and improve the load capacity of the device.
Due to the abandonment of the traditional generation principle of three-phase five column triple frequency generators, the following advantages have been brought about:
1. Small size, light weight, easy to carry, and convenient for high-power conversion.
Not only can it generate three times the frequency, but it can also produce test voltage outputs of 1, 2, 3, and 4 times the frequency.
3. The operation and wiring are simple, which greatly reduces the requirements for the capacity of the on-site test power supply.
Previous No more